Add up the running watts of everything that has to run at the same time, then add the extra starting surge of the single biggest motor. That total is the starting watts your generator must cover.
For a home keeping a refrigerator, a sump pump, a gas furnace blower, lights and Wi-Fi going, three manufacturer charts put that number between about 3,450 and 5,025 starting watts. That gap is the interesting part. We'll show you how to close it with your own appliance labels.
Charts checked live on November 9, 2026. Manufacturers update these pages, so treat our numbers as a starting point and your appliance labels as the final word.
Running watts vs. starting watts: what's the difference?
Running watts are what an appliance draws once it's going. Starting watts (also called surge watts) are the short burst a motor needs to get moving, usually for a few seconds.
Only things with a motor or compressor surge: refrigerators, freezers, sump pumps, well pumps, furnace blowers and air conditioners. Lights, chargers, space heaters and microwaves draw the same to start as to run. Champion's wattage chart marks heaters, microwaves, lights and chargers as needing no extra starting watts.
Every generator also lists two numbers. Honda's EU2200i, a small inverter generator (the quieter type Honda describes as giving stable, clean power), is rated 1,800 watts running and 2,200 watts maximum. The running number is what it can hold for hours. The maximum is what it can give for a moment while a motor starts.
How do I add it up?
Four steps. A pencil and the back of an envelope are enough.
- List only what must run at the same time. The fridge and the furnace blower, yes. The microwave can wait until something else is off.
- Add the running watts of everything on that list.
- Find the one motor with the biggest extra surge (its starting watts minus its running watts). Add that once. Two motors starting in the same second is the case you avoid by switching them on one at a time.
- Pick a generator whose running rating beats step 2 and whose starting rating beats step 2 plus step 3.
Generac's portable generator brochure uses this same method and notes that its totals assume "intermittent starting of devices." Honda's power management page makes the same point with a worked example: start the fridge and furnace at different times and you need far less than the sum of their starting watts.
Why do generator wattage charts disagree?
We pulled the refrigerator, 1/2 horsepower (hp) sump pump and 1/2 hp furnace blower rows from three manufacturers' own charts on November 9, 2026.
| Appliance | Honda (running / starting) | Generac (running / extra to start) | Champion (running / starting) |
|---|
| Refrigerator | 132-192 / 1,200 | 700 / +2,200 | 150-400 / 800-1,200 |
| Sump pump, 1/2 hp | 1,050 / 2,150 | 1,050 / +2,150 | 800-1,050 / 1,300-2,150 |
| Furnace blower, 1/2 hp | 875 / 2,350 | 875 / +2,300 | 300-800 / 800-1,600 |
Read the column headings closely, because the charts don't even measure the same thing. Honda and Champion list total starting watts. Generac lists *additional* starting watts, on top of running watts. So Generac's refrigerator needs about 2,900 watts for a moment, while Honda's needs 1,200.
The pages themselves show why the rows differ. Honda's refrigerator row is specifically labeled Energy Star. Generac's row is a generic "Refrigerator/Freezer," and it reads like a conservative planning number meant to cover whatever fridge you happen to own. Champion gives ranges to cover many models. Honda's own pages don't agree with each other either: its wattage guide lists the fridge at 1,200 starting watts, and its power management example uses 1,600.
So what does that do to the answer?
We ran the same household through all three charts using the method above: refrigerator, 1/2 hp sump pump, 1/2 hp furnace blower, plus 100 watts for a few LED bulbs, the router and phone charging (our assumption, the same for every chart). For Champion we used the high end of each range.
| Chart used | Running watts | Starting watts needed |
|---|
| Champion (high end) | 2,350 | 3,450 |
| Honda | 2,217 | 3,692 |
| Generac | 2,725 | 5,025 |
Same house, same method, and the answer moves by about 1,600 watts. In our read, that's the difference between a mid-size portable and a big one, with the fuel use, weight and price that come with it.
The fridge alone shows the gap most clearly. On Honda's numbers, a fridge plus lights and Wi-Fi needs about 1,300 starting watts. On Generac's, about 3,000. Honda lists the EU2200i (2,200 watts max) as able to run an Energy Star fridge. Generac's generic row would say that same generator is too small. Both can be right, for different refrigerators.
How do I find my own appliance's real wattage?
This is how you settle the disagreement for your house instead of picking a chart and hoping.
- Read the label. Fridges, pumps and furnaces carry a nameplate, often inside the fridge door, on the pump motor or inside the furnace panel. If it lists only amps, multiply by 120 for a 120-volt appliance. Generac's own 3,500-watt generator spec sheet gives that rule: 15 amps times 120 volts is 1,800 watts.
- Know what the label may not tell you. If yours lists no starting watts, using the most conservative chart row for that appliance is the safer guess. An undersized generator can bog down or trip its breaker when the fridge compressor kicks on.
- Check the horsepower. Sump pumps and furnace blowers come in 1/3 and 1/2 hp versions, and the charts treat them very differently. Honda lists a 1/3 hp sump pump at 1,300 starting watts and a 1/2 hp at 2,150.
- Check whether it plugs in. A fridge plugs into a cord. If your furnace or well pump has no plug, it needs a transfer switch to run on a generator (more on that below).
What size generator do I need for common setups?
These ranges come from the manufacturer charts above. Your labels can move them.
| What you want to run | Rough starting watts | What that usually means |
|---|
| Fridge, lights, phones, Wi-Fi | 1,300-3,000 | A 2,000-3,000 watt inverter generator may do it if your fridge is efficient |
| Fridge, 1/2 hp sump pump, 1/2 hp gas furnace blower, lights, Wi-Fi | 3,450-5,025 (our table above) | A mid-size portable, staggered starts, and a transfer switch if the furnace has no plug |
| Well pump (1 hp) | 2,000-4,000 for the pump alone (Champion) | Size the whole list around it |
| Central air (3 ton) | 5,000-6,000 for the AC alone (Champion) | A large portable or a standby unit |
| Electric water heater | 4,500 running (Honda) | Plan to skip it on a portable |
An electric water heater at 4,500 watts is more than double the EU2200i's 1,800-watt running rating.
What about fuel and run time?
Bigger isn't free. The EU2200i runs 3.2 hours on its 0.95-gallon tank at its rated load and 8.1 hours at a quarter load, per Honda's spec sheet. Running a generator near its limit means more refueling. Ready.gov says let the generator cool before refueling, because fuel spilled on hot engine parts can ignite.
So the real sizing question has two parts: enough watts for the starting surge, and enough fuel on hand for the hours you expect to be dark. If a winter storm or high wind is in the forecast, that's your window to fill fuel cans and test-run the generator. You can check active National Weather Service alerts for any ZIP code with no sign-in at GridPrepped Alerts. With a free sign-in you can get email alerts for up to five locations, each with its own severity setting, under your profile.
How do I connect a generator safely?
Sizing is only half the job. Three rules from federal guidance (we walk through the clearance, carbon monoxide alarm, and backfeeding rules in how to run a generator safely):
- Outside only. CPSC says never run a portable generator inside a home or garage, even with doors and windows open, and to keep it at least 20 feet from the home with the exhaust pointed away (CPSC carbon monoxide page). Ready.gov adds windows, doors and attached garages to that 20 feet.
- CO alarms. Both CPSC and Ready.gov call for battery-powered or battery-backup carbon monoxide alarms on every level of the home.
- No backfeeding. OSHA says never attach a generator directly to the electrical system of a structure unless a qualified electrician has properly installed it with a transfer switch. Doing so can energize wiring for great distances and create a risk of electrocution for utility workers (OSHA, Using Portable Generators Safely). Otherwise, plug appliances directly into the generator with grounded (3-prong) extension cords rated for the load.
If you rent, the transfer switch may not be your call. A fridge on an extension cord from a generator outside, or a battery power station for phones and Wi-Fi, still covers a lot.
Have you actually started it under load?
A generator that has never powered your real fridge is a guess. The cheapest test is a dry run on a nice day: start it, plug in the fridge, then switch on the next item and watch whether it bogs down when the compressor cycles.
If you want to see where backup power fits in the rest of your readiness, the free GridPrepped readiness assessment scores your household across six layers, including a Test/Practice layer, and gives you a Grid Score at the end. No sign-in needed. It draws four questions per layer from a larger set, so the question about testing backup power may or may not come up in your session. Test it anyway.